AC Din Rail-mounted Multi-Channel Multi-circuitus Energy Meter SPM20 60A 220V pro ambitu ratio magna

Din-rail type AC industria metri

AC Din Rail-mounted Multi-Channel Multi-circuitus Energy Meter SPM20 60A 220V pro ambitu ratio magna

1. Magnitudo parva - in artissimo puncto institui potest, integrare institutiones spatio constrictas existentes.

2. Ultra-pacto Design - Consista de potestate unitatis et sensoriis currentis (cum RJ12 portu, core solido libito vel core scisso )

Lata mensurae 3. - Max, Support 63A

4. Multi Circuitus - Support 30 Circuitus unius Phase seu 10 tres Phase circuii AC mensurae

5. High Accuracy -Voltage & Current classis 0.5, kWh classis 1.0

6. Multi Network Type - 1 tempus 2 filis, 3 tempus 4 filum

      Praecipua Documenta

      Compatible Software

      PiEMS System1vwd

      Dolor PiEMS Ratio

      Product Introduction

      Gubernator SPM20-wxq
      • SPM20 CE sub-metering certificata est, apta potestati distribuendi scrinium ac scrinium distribuendi inferioris voltages minor quam AC 220V mutandum est, et sustentaculum ad singulae periodi duo fila et tria phase quattuor filis systematis.

        Plene sequuntur EMC Latin:
        IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-11,IEC62052-11 2003, et CISPR22:2006.

        Quaelibet iuncturas metrorum: Single-Phase et Tres Phase possibiles sunt permittens utentes flexibilitatem praebere cum institutionibus systematum electrica metrorum. Installatio fit utens Transformers (CT).
      Gubernator SPM20-13tz
      • SPM20 CMS systema monitorium praesertim potentiae terminalis est, a micro circumitu multi- gyri unitas vigilantia distributa. Mensura moduli et imperium moduli consistit, et hi duo moduli a PLbus communibus coniunguntur, quae etiam a gubernatore investigentur, et obturaculum iungo est a norma RJ12 qui institutionem in situ simpliciorem reddere potest.
      SPM20wersh4
      • SPM20 late utendum est in Hotel, Cura, Dormitorium, Aedificium Commercial, Officium, Aedificium residentiale, ac Project Reconstructionem. Una unitas magna vigilantia potest 30pcs mensurationis modulorum plus sustinere, et 10 tres phases circuitus vel 30 circulos unius periodi monitoria subire, et munus mensurare et metering ad generalem notam trium Phase rami (potestatis generalis, totalis electrici-energiae. ). Mensura currentis eius in maximo 63A est, diversam applicationem in situ explere potest.
      Gubernator SPM202-xce
      • Micro distributio multi-circuitus mensurae unitatis multiplex institutioni esse potest, et moderator ad DIN35 inaugurali institutionem conformat, et cochleae fixationi backboard install; In linea institutionis clausae sunt et fibula aperiens ascendens ad optionem quod erat faciendum. Connexio inter mensurae unitatis et moderatoris est ad portum RJ12 vexillum, facile ordinationem in situ wiring facere potest.

        SPM20 praebet principale munus ut infra

      • 1.Realtime Mensurae intentione, Current, Active potentia, Reactiva potentia, Apparens potentia, Factor potentia, Frequency
        2.Energy Consummatio Active navitas, Reactivum industria
        3.Alarm Function ONERO, Sub onere, Super current, Sensor culpa
        4.Communicatio 1 RS485 port, MODBUS-RTU protocol
      • wi7n

      Specification

      SPM20-M: Main Module

      Connection Modus

      I tempus 2wires, III tempus IV filis

      Potestas Supply

      Copia sui, per A phase

      Voltage Input

      1 tempus 2 filis 220V Range:40%-150%
      III tempus 4wires 3×220/380V Teli;40%-1509%

      Frequentia

      45~65Hz

      Potestas Damnum

      Virtus copia ambitus: 10W

      Communicationis

      RS485 Vide, auxilium Modbus-RTU Baudrate: 4800,9600,19200bps Inscriptio: 1~247

      SPM20-C: Solidum Core Sensor SPM20-O: Split Core Sensor
      Connection Modus Bus connexionis (2xRJ12 Portus) Connection Modus Bus nexum (2xRJ12Port)
      Input Current Rated 5(63)A Input Current Rated 10(50)A
      Institutionem Solidum core Institutionem Scinditur Core
      Apertum foramen Φ8 mm Apertum foramen Φ9.5 mm
      Sampling Rate 28k Hz Sampling Rate 28k Hz
       
      Parameter Sagaciter mensuræ Rang
      Voltage 0.5% 40%~ 120%
      Current Core solidum Sensor (C *) 0.5% 0-63A,1%~120%
      Scinditur Caput Sensor (O *) 1.0% 0-50A,1%~120%
      Potestas factor 1.0% -1~1
      Active potentia 1.0% Single phase:0~±14kW/var/VA Total:0~±42kWvar/VA
      Reactivum powis 2.0%
      Apparens potentia 2.0%
      Active industria Core solidum Sensor (C *) 1.0% 0-99,999,999,9 kWh
      Scinditur Caput Sensor (O *) 2.0% 0~99,999,999.9 kWh
      Reactivumindustria 2.0% 0~99,999,999.9 kVarh
      Frequentia 0.01 45~65Hz
      Potestas frequentia sustinere voltage 2000VAC Environment Normalis temperatura operating:-20℃~+55℃ Temperatura operans:-20℃~+50℃ Repono temperies: -30℃~+80℃ Umor:
      egonsulation resistentia ≥100MΩ
      Impetus sustinere voltage 6kV(apicem)
      IP index P52(pane ante)
      Standard (EMC)
      Electrostatica missio testium immunitatis IEC 61000-4-2, Level 4 radiatum radio-frequency immunitatis campi electromagnetici (RFEMS) IEC61000-4-3,Level4 Electrical ieiunium fluxum test IEC61000-4-4,Level4 Surge testium immunitatis (1,2/50μs ~8/20μ) IEC61000-4-5,Level4 Conductio commotio rejectio agri inductionis radiophonicae frequentiae
      Electromagnetica emissio fines intentione sag et brevi temporis immunitatem interpellare Power frequentiam voltage sustinere IEC61000-4-6,Level 3 CISPR22:2006,Pass IEC61000-4-11,Transi IEC 62052-11 2003